The Provision & use of work Equipment Regulations 1998 requires every employer to ensure that equipment is suitable for the use for which it is provided (Reg 4 (1)) and only used for work for which it is suitable (Reg 4 (3)). They require every employer to ensure equipment is maintained in good order (Reg 5) and inspected as necessary to ensure it is maintained in a safe condition (Reg 6).
Apart from the legal obligation to ensure the safety of persons using electrical appliances, should an accident / incident or fire result from faulty electrical appliance your insurance may be invalid.
Alan Brown
Mobile: 07525 043 444
alan@safesure-electrical.co.uk
18 Dryden avenue
Daventry
Northamptonshire
NN11 9DJ
We are family run business based within the midlands; we have more than 27years experience in the electrotechnical environment or aim is to offer a professional dependable services at a competitive price, around 70% of or business is repeat/referral work from happy clients.
Our technicians have completed in the excess of 3years training to archive City and Guilds/NVQ standard so you can be guaranteed of a quality service. We are more than happy to provide references from previous clients should you require them.
We cover the the whole of the following areas; Leicester, Coventry, Rugby, Banbury, Northampton ect.
Electrical testing of portable equipment will involve the following:
(i) Earth bond continuity tests
(ii) Insulation resistance testing
(iii) Functional checks
(a) Earth Bond Test (Class 1 equipment only):
Readings should show less than 0.1+R Ohms (where R is the resistance of the lead)
Tested at a current of 1.5 times the rating of the fuse and no greater than 25A for a period of between 5 and 20 seconds or with a short-circuit test current within the range 20mA to 200mA.
(b) Insulation Resistance Test:
The applied test voltage should be approximately 500 Vdc
Class 1 heating equipment < 3kW 0.3M Ohms
Class 1 All other equipment 1M Ohms
Class 2 Equipment 2M Ohms
Class 3 Equipment 250k Ohms
(c) Optional Tests:
Flash Test: No flashover or breakdown shall occur
Operation/Load test: Compare reading with stated details on nameplate
Earth leakage test:
Class 1 Handheld Appliances 0.75mA
Other Class 1 Appliances 3.5mA
Class 2 Appliances 0.25mA